Abstract. Air conditioning is the largest electricity consumer in a house, so how to achieve maximum air quality healthy and comfortable with minimum air-conditioning energy consumption should be considered. Air conditioning energy efficiency can be achieved primarily from the design of the building. In this article the building uses b-panel®. b-panel® is a double layer of reinforced concrete panel which is specially designed with a layer of expanded polystyrene insulation (EPS) in the middle. Figure 1 illustrates a house made of b-panel®.Factors that affect the cooling load in the room are the altitude, solar radiation, the orientation of the location of the building which affects the absorption of radiation, the color on the walls of buildings, and other supporting material quality (like the glass in the window). Therefore, the saving that occurs for the cooling load in the highlands (Bandung) and the coastal areas (Jakarta) will be different. This article presents the analysis of this difference.
Figure 1 – House with b-panel® system
Indonesia is a humid tropical country. This conduces that many regions in Indonesia have to use air conditioning to obtain thermal comfort because it is not enough if the building uses only natural ventilation. Negative characteristics in humid tropical climate which cause unreliable natural ventilation for thermal comfort are:
Therefore, in order to obtain thermal comfort in the room is to use artificial ventilation, such as air-conditioning (A / C). The advantages of using A/C are:
However, there are some losses caused by the use of A/C. Among these are:
The main task of the use of A/C is to carry the heat from the room to the outdoors. Therefore, the heat that comes into the room or that arises in the space should be as little as possible.One way to reduce the incoming heat is to use building materials that can withstand ambient temperature and solar load entering the room as much as possible (having a low transmittance value), such as using a expanded polystyrene(EPS) insulation. b-panel® is a double layer of reinforced concrete panel which is specially designed with a layer of EPS insulation (EPS) in the middle.The use of b-panel® in building can block the propagation of heat from the outdoor. This will impact positively to the reduction of energy consumption A/C, so that residents can save money on electricity cost.
Here is a diagram of the components of heat into the room and the heat generated in the room. These components are required to calculate the required cooling load in the room. Furthermore, it is used to determine the A/C model used with adequate cooling capacity of A/C.
Figure 2 – Heat components (Source: www.egydown.com)
In this article saving A/C which occurs if the b-panel® is used as a building material in the highland (Bandung) and the coastal area (Jakarta) will be discussed. Here are data from the city of Bandung thermal comfort:
Here are the thermal comfort fatcs of Jakarta:
For ease of analysis, the limits of the room to calculate the cooling load will be made. Cooling load is calculated for each building using b-panel® and red brick in Jakarta and Bandung.There is a house with a length = 8 m, width = 8 m, and height = 3.2 m with 4 room where three rooms is fitted with A/C and 1 room is not is fitted with A/C. All rooms are identical and have a window (see Figure 3 and Figure 4).
Figure 3 – House front view
Figure 4 – House plan
Wall have a thickness of 15 cm. Each room has two walls in direct contact with the outside air. Room A and room C has a wall associated with the air in the room without A/C, while the B room has 2 walls associated with the air in the room is fitted with A / C (which means no thermal flow). This house uses roof deck. Two types of wall are analyzed:
Table 1 – Absorption of solar radiation values for external walls and opaque roofa
(sumber: www.jurnalinsinyurmesin.com)
Outer walls and roof deck were painted with medium yellow color αpaint = 0,58. If the outside walls were painted with different color, it will give the different absorption of solar radiation value (α), as shown in Table 2 below:
Table 2 – Absorption of solar radiation values for the paint on the surface of the outer wall
(Source : www.jurnalinsinyurmesin.com)
On the walls glass windows were fitted with the glass length = 0.9 m and the glass height = 1.5 m (Uglass = 4,48 W/m2 oC, from the factory brochure). The average incidence angle of the sun coming through the walls and windows are assumed ß = 75o and the window has a Φ = 0.75.
These other data along with a brief explanation are required for cooling load calculation if the building is planned in two different cities, namely Jakarta and Bandung:
The following is a table of data measurement result of solar radiation intensity across Indonesia by BPPT and BMKG from 1965 to 1995.
Table 3 – The intensity of solar radiation in Indonesia
Source: ‘Analisis Potensi Pembangkit Listrik Tenaga Surya di Indonesia’
By Irawan Rahardjo and Ira Fitriana
Known average solar radiation = I = 1000 W/m2. This is the average solar radiation power in Indonesia.
Table 4 – Air change rate
(Source: www.wikipedia.com)
Ventilation = 3 ACH (Air Change Hour)
Table 5 – Climate data in Bandung (Source: www.bmkg.co.id)
Table 6 – Climate data in Jakarta (Source: www.bmkg.co.id)
The following is analysis of cooling load calculation that are required in both places. Calculation is derived from the dictates of Buildings Completed Systems Subjects prepared by Ir. Paulus A. S., MT. The figure below shows that heat into the room.
Figure 5 – Diagram of source of heat into the room
Cooling load calculation of the red-brick building in the coastal area (Jakarta):
The formula used is Qm = Qi + Qs + Qc + Qv . . Heat that need to transfer: heat inside room + solar heat penetrated glass/window + heat outside penetrated wall + heat from outside. Here are the calculations for room A and room C.
Calculate first Δglass and Δdinding :
Δ Twall by calculating the average absorption of plastered and coated brick:
Wall surface temperature outside
Thus Δ Tdinding = 38,01 – 20 = 18,010C
Cooling Load:
Qm= 162 + 2095,91 + 471,84 = 3742,25 W. Thus, the heat that must be transported out of the room A and room C is respectively 3742,25 W. In the same way, the required cooling load to room B is:
Qi = 162 W
Qs = 1012,5 W
Qc = 1900,07 W
Qv = 471,84 W
Qm = 162 + 1012,5 + 1900,07 + 471,84 = 3546,41 W. The heat that must be transported out of the room B is 3,55 kW. Thus, the cooling load required for this house is = 3742,25 W + 3742,25 W + 3546,41 W = 11030,91 W = 11,03 kW.
Cooling load calculation of the b-panel® ® building in the coastal area (Jakarta):
Here is the calculation for room A and room C:
Qi = 162 W
Qs = 1012,5 W
Qc = 368,99 W
Qv = 471,84 W
Qm = 162 + 1012,5 + 368,99 + 471,84 = 2015,33 W. Thus, the heat that must be transported out of the room A and room C is respectively 2015,33 W. In the same way, the required cooling load to room B is:
Qi = 162 W
Qs = 1012,5 W
Qc = 338,27 W
Qv = 471,84 W
Qm = 162 + 1012,5 + 338,27 + 471,84 = 1984,61 W. The heat thatmust be transported out of the room B is 1984,61 W. Thus, the cooling load required for this house is = 2015,33 W + 2015,33 W + 1984,61 W = 6015,27 W = 6,02 kW.
Cooling load calculation of the red-brick building in the highland (Bandung):
Here is the calculation for room A and room C:
Qi = 162 W
Qs = 1012,5 W
Qc = 1530,61 W
Qv = 249,80 W
Qm = 162 + 1012,5 + 1530,61 + 249,80 = 2954,91 W. Thus, the heat that must be transported out of the room A and room C is respectively 2954,91 W. In the same way, the required cooling load to room B is:
Qi = 162 W
Qs = 1012,5 W
Qc = 1465,33 W
Qv = 249,80 W
Qm = 162 + 1012,5 + 1465,33 + 249,80 = 2889,63 W.The heat thatmust be transported out of the room B is 2889,63 W. Thus, the cooling load required for this house is = 2954,91 W + 2954,91 W + 2889,63 W = 8799,45 W = 8,80 kW.
Cooling load calculation of the b-panel® building in the highland (Bandung):
Here is the calculation for room A and room C:
Qi = 162 W
Qs = 1012,5 W
Qc = 259,92 W
Qv = 249,80 W
Qm = 162 + 1012,5 + 259,92 + 249,80 = 1684,22 W. Thus, the heat that must be transported out of the room A and room C is respectively 1684,22 W. In the same way, the required cooling load to room B is:
Qi = 162 W
Qs = 1012,5 W
Qc = 249,68 W
Qv = 249,80 W
Qm = 162 + 1012,5 + 249,68 + 249,80 = 1673,98 W. The heat thatmust be transported out of the room B is 1673,98 W. Thus, the cooling load required for this house is = 1684,22 W + 1684,22 W + 1673,98 W = 5042,42 = 5,04 kW.
Table 7 – Required cooling load
By using the b-panel®cooling load can be reduced by 45,5% in Jakarta and by 42,7% in Bandung to the building with red brick. Below is a comparison chart of the required cooling load between Bandung and Jakarta.
Figure 6 – Cooling load chart in Bandung and Jakarta
Conclusion. The use of b-panel® consistently and significantly lowers cooling load more than 40% in both coastal areas (Jakarta) and the highlands (Bandung). The average temperature differences in the two cities cause different A/C load. However, drastic improvement of A/C power consumption occurs when the entire surfaces of the walls and roof deck in direct contact with the outside wrapped with a layer of insulation, such as the presence of EPS in the b-panel® system.
Related News: